Chapter 12 Description of Parameter SettingsMS300
09 Communication Parameters
If the AC motor drive is controlled by RS-485 serial communication, the communication address
for this drive must be set via this parameter and each AC motor drive's communication address
must be different.
This parameter is for setting up the transmission speed of computer and the drive.
Please set 4.8 Kbps, 9.6 Kbps, 19.2 Kbps, 38.4 Kbps, 57.6 Kbps, or 115.2 Kbps. Otherwise the
transmission speed will be replaced by 9.6 Kbps.
This parameter is to set the reaction of MODBUS transmission errors with the host. Detection
time can be set in Pr. 09-03.
It is used to set the communication transmission time-out.
CALL NOW 800-985-6929
http://www.deltaacdrives.com
When us ing communication devi ces,
connects AC dr ive with P C by us ing
Delta IFD6530 or IFD 6500.
Communication Address
Settings
1~254
COM1 Transmission Speed
Settings
4.8~115.2 Kbps
COM1 Transmission Fault Treatment
Settings
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning and continue operation
COM1 Time-out Detection
Settings
0.0~100.0 sec.
COM1 Communication Protocol
1: 7N2 (ASCII)
Settings
2: 7E1 (ASCII)
3: 7O1 (ASCII)
4: 7E2 (ASCII)
5: 7O2 (ASCII)
6: 8N1 (ASCII)
7: 8N2 (ASCII)
8: 8E1 (ASCII)
http://www.deltaacdrives.com
The parameter can be set during the operation.
8
1
Modbus RS- 485
Pin 1~2,7,8: Reserv ed
Pin 3, 6: GND
Pin 4: SG-
Pin 5: SG+
RS-485
12.1-09-1
Email: info@deltaacdrives.com
Factory Setting: 1
Factory Setting: 9.6
Factory Setting: 3
Factory Setting: 0.0
Factory Setting: 1