CALL NOW 800-985-6929
Chapter 12 Description of Parameter SettingsMS300
Both external terminal JOG and key "F1" on the keypad KPC-CC01 (optional) can be used to set
JOG function. When the JOG command is ON, the AC motor drive will accelerate from 0 Hz to
JOG frequency (Pr. 01-22). When JOG command is OFF, the AC motor drive will decelerate from
Jog frequency to stop. The JOG accel. / decel. time (Pr. 01-20, Pr. 01-21) is the time that
accelerates from 0.0 Hz to JOG frequency (Pr. 01-22). The JOG command cannot be executed
when the AC motor drive is running. In the same way, when the JOG command is executing,
other operation commands are invalid.
This function does not require external terminal switching function, it will switch the accel. / decel.
time automatically by Pr. 01-23 setting. If the external terminal is set, it will be prior to Pr. 01-23.
When using this function, please set S-curve acceleration time as 0 if 4
too short.
This parameter is used to set slow start when the drive begins to accelerate at start. The accel. /
decel. curve can adjust the S-curve accel. / decel by setting parameter value. When it is enabled,
the drive will have different accel. / decel. curve by the accel. / decel. time.
The S-curve function is disabled when accel. / decel. time is set to 0.
When Pr. 01-12, 01-14, 01-16, 01-18 Pr. 01-24 and Pr. 01-25,
the actual accel. time = Pr. 01-12, 01-14, 01-16, 01-18 + (Pr. 01-24 + Pr. 01-25) / 2
CALL NOW 800-985-6929
http://www.deltaacdrives.com
JOG Frequency
Settings
0.00~599.00 Hz
st
th
1
/ 4
Accel. / decel. Frequency
Settings
0.00~599.00 Hz
Freq uen cy
1s t Accel eration
Ti me
01-23
4th Ac celeration
Time
1st/4th Ac celeration/Decel er ation F r equenc y Switching
S-curve Acceleration Begin Time 1
S-curve Acceleration Arrival Time 2
S-curve Deceleration Begin Time 1
S-curve Deceleration Arrival Time 2
Settings
Pr. 01-45 = 0: 0.00~25.00 sec.
Pr. 01-45 = 1: 0.0~250.0 sec.
http://www.deltaacdrives.com
1st D eceleration
Time
4th D eceleration
12.1-01-9
Email: info@deltaacdrives.com
Factory Setting: 6.00
Factory Setting: 0.00
th
acceleration time is set
Time
Time
Factory Setting: 0.20 / 0.2
Email: info@deltaacdrives.com