Digital Input / Output Parameter; 2-Wire / 3-Wire Operation Control - Delta MS300 Series User Manual

Standard compact drive
Hide thumbs Also See for MS300 Series:
Table of Contents

Advertisement

CALL NOW 800-985-6929

02 Digital Input / Output Parameter

 In Quick Start function, the output will remain ready for operation. The drive will respond to start
command immediately.
 When using Quick Start function, there will be greater potential voltage on the output terminals.
 This parameter is for setting the configuration of external drive operation control, plus Quick Start
function, there are six different control modes:
CALL NOW 800-985-6929
http://www.deltaacdrives.com

2-wire / 3-wire Operation Control

Settings
0: No function
1: 2-wire mode 1, power on for operation control
(M1: FWD / STOP, M2: REV / STOP)
2: 2-wire mode 2, power on for operation control
(M1: RUN / STOP, M2: REV / FWD)
3: 3-wire, power on for operation control
(M1: RUN, M2: REV / FWD, M3: STOP)
4: 2-wire mode 1, fast start up
(M1: FWD / STOP, M2: REV / STOP)
5: 2-wire mode 2, fast start up
(M1: RUN / STOP, M2: REV / FWD)
6: 3-wire,fast start up
(M1: RUN, M2: REV / FWD, M3: STOP)
IMPORTANT
1. In fast start up function, terminal output will keep in ready status, drive will
response to the command immediately.
2. When using fast start up function, the output terminal will have higher
voltage potentially.
Pr. 02-00
Setting value: 1
2-wire
FWD / STOP
REV / STOP
Setting value: 2
2-wire
RUN / STOP
REV / FWD
http://www.deltaacdrives.com
Chapter 12 Description of Parameter SettingsMS300
 This parameter can be set during operation.
Control Circuits of the External Terminal
FWD / STOP
REV / STOP
RUN / STO P
FWD / REV
12.1-02-1
Email: info@deltaacdrives.com
Factory Setting: 1
"OPEN": STOP
MI1
"CLOSE" : FWD
MI2
"OPEN": STOP
"CLOSE": REV
DCM
M300
"O PEN": STO P
MI1
"CLO SE": RUN
MI2
"O PEN": FWD
"CLO SE": REV
DCM
M300
Email: info@deltaacdrives.com

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents