Chapter 12 Description of Parameter SettingsMS300
This parameter determines the behavior when 4~20 mA signal is loss, when ACIc (03-29 = 0).
When Pr. 03-29≠0, it means the voltage input to ACI terminal is 0~10V or 0~20mA. At this
moment, Pr. 03-19 will be invalid.
When setting is 1 or 2, it will display warning code "ANL" on the keypad. It will be blinking until the
loss of the ACI signal is recovered.
When the motor drive stops, the condition of warning does not exist, then the warning will
disappear.
Function Chart
Settings
0
Output frequency (Hz)
1
Frequency command (Hz)
2
Motor speed (Hz)
3
Output current (rms)
4
Output voltage
5
DC BUS voltage
6
Power factor
7
Power
9
AVI
10
ACI
12
Iq current command
13
Iq feedback value
14
Id current command
15
Id feedback value
CALL NOW 800-985-6929
http://www.deltaacdrives.com
Signal Loss Selection of Analog Input 4-20 mA
Settings
0: Disable
1: Continue operation at the last frequency
2: Decelerate to 0 Hz
3: Stop immediately and display ACE
Multi-function Output 1 (AFM)
Settings
0~23
Functions
http://www.deltaacdrives.com
Descriptions
Max. frequency Pr. 01-00 is regarded as 100 %.
Max. frequency Pr. 01-00 is regarded as 100 %.
Max. frequency Pr. 01-00 is regarded as 100 %
(2.5 X rated current) is regarded as 100 %
(2 X rated voltage) is regarded as 100 %
450V (900V) = 100 %
-1.000~1.000 = 100 %
(2 X rated voltage) is regarded as 100 %
0~10 V = 0~100 %
4~20 mA = 0~100 %
(2.5 X rated current) is regarded as 100 %
(2.5 X rated current) is regarded as 100 %
(2.5 X rated current) is regarded as 100 %
(2.5 X rated current) is regarded as 100 %
12.1-03-14
Email: info@deltaacdrives.com
Factory Setting: 0
Factory Setting: 0