Over-Torque Detection Selection (Motor 2); Over-Torque Detection Time (Motor 2) - Delta MS300 Series User Manual

Standard compact drive
Hide thumbs Also See for MS300 Series:
Table of Contents

Advertisement

CALL NOW 800-985-6929
 When Pr. 06-06 and Pr. 06-09 are set to 1 or 3, warning message will be displayed but there will
not be an abnormal record.
 When Pr. 06-06 and Pr. 06-09 are set to 2 or 4, warning message will be displayed and there will
be an abnormal record.
 When the output current exceeds over-torque detection level (Pr. 06-07 or Pr. 06-10) and also
exceeds over-torque detection time (Pr. 06-08 or Pr. 06-11), the over-torque detection will follow
the setting of Pr. 06-06 and Pr. 06-09.
When Pr. 06-06 or Pr. 06-09 is set to 1 or 3, there will be ot1 / ot2 warning displayed while the
drive will keep running. The warning will be off only until the output current is smaller than 5 % of
the over-torque detection level.
CALL NOW 800-985-6929
http://www.deltaacdrives.com

Over-torque Detection Selection (Motor 2)

Settings
0: No function
1: Continue operation after Over-torque detection during constant speed
operation
2: Stop after Over-torque detection during constant speed operation
3: Continue operation after Over-torque detection during RUN
4: Stop after Over-torque detection during RUN
Over-torque Detection Level (Motor 1)
Settings
10 to 250 % (100 % corresponds to the rated current of the drive)
Over-torque Detection Level (Motor 1)
Settings
0.0~60.0 sec.
Over-torque Detection Level (Motor 2)
Settings
10~250 % (100 % corresponds to the rated current of the drive)

Over-torque Detection Time (Motor 2)

Settings
0.0~60.0 sec.
Ov er-t orque
det ect ion level
06- 07( 0 6- 10 )
0 6- 07( 0 6- 10) * 9 5%
Multi-fu nct ion output
terminal=7 or 8
http://www.deltaacdrives.com
Chapter 12 Description of Parameter SettingsMS300
Out put current
ON
Over-t orque
detection time
06-08(06-11)
12.1-06-5
Email: info@deltaacdrives.com
Factory Setting: 0
Factory Setting: 120
Factory Setting: 0.1
Factory Setting: 120
Factory Setting: 0.1
O N
Email: info@deltaacdrives.com

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents