11 Advanced Parameters
In this parameter group, ASR is the abbreviation for Adjust Speed Regulator.
 bit 7 = 0: frequency is saved before power turns off. When power turns ON again, the displayed
frequency will be the memorized frequency.
bit 7 = 1: frequency is not saved before power turns off. When power turns ON again, the
displayed frequency will be 0.00 Hz.
 When setting is 2-phase mode, it can reduce the drive power components losses effectively and
provide better performance in the long wire applications.
 When setting is space vector mode, it can reduce the power loss and electromagnetic noise of
motor effectively.
bit No.
0
Reserved
1
FWD / REV action control
2~15
Reserved
CALL NOW 800-985-6929
http://www.deltaacdrives.com

System Control

Settings
bit 3: Dead time compensation closed
bit 7: Selection to save or not save the frequency

ASR 1 Gain

Settings
0~40 Hz (IM) / 1~100 Hz (PM)
ASR 1 Integral Time
Settings
0.000~10.000 sec.

PWM Mode Selection

Settings
0: 2-phase
2: Space vector
System Control Flag
Settings
0000~FFFFh
Function
http://www.deltaacdrives.com
 This parameter can be set during operation.
0: FWD / REV cannot be controlled by Pr. 02-12 bit 0 & 1
1: FWD / REV can be controlled by Pr. 02-12 bit 0 & 1
12.1-11-1
Email: info@deltaacdrives.com
Factory Setting: 0
Factory Setting: 10
Factory Setting: 0.100
Factory Settings: 2
Factory Settings: 0000
Description