CALL NOW 800-985-6929
Chapter 17 Safe Torque Off FunctionMS300
17-6
Timing Diagram Description
The following timing diagram shows the status of relevant signals under different conditions:
17-6-1 Normal operation status
As shown in Figure 4: When S1~DCM and S2~DCM is ON (STO function is not required), the
drive will execute "Operating" or "Output Stop" according to RUN command.
17-6-2-1 STO, Pr. 06-44=0, Pr. 02-35=0 (Selection of external control operation after
reset / power on, 0=not valid)
As shown in Figure 5: When both of S1~DCM and S2~DCM are OFF during operation
(STO function is required), the drive will stop outputting when enter safe mode regardless
of Run command is ON or OFF status.
RUN co mmand
CALL NOW 800-985-6929
http://www.deltaacdrives.com
RUN command
S1~DCM
input status
S2~DCM
input status
Drive out put
RUN
O N
S1~DCM
input status
S2~DCM
O N
input status
Drive out put
Operat i n g Output stop
http://www.deltaacdrives.com
STOP
RUN
ON (no S TO f unct ion n eed Pr. 0 6-44=0 )
ON (STO function is not required, Pr. 06-44=0)
ON (STO function is not required, Pr. 06-44=0)
ON (no S TO f unct ion n eed Pr. 0 6-44=0 )
Output stop
Operat ing
Figure 4
ON
O FF
O N
O FF
Figure 5
17-6
Email: info@deltaacdrives.com
,
,
STOP
RUN
Email: info@deltaacdrives.com