The AUTO / HAND mode can be switched by the keypad KPC-CC01 (optional) or multi-function
input terminal (MI) to set the source of the master frequency.
Pr. 00-20 and Pr. 00-21 are for the settings of frequency source and operation source in AUTO
mode. Pr. 00-30 and Pr. 00-31 are for the settings of frequency source and operation source in
HAND mode.
The factory setting of frequency source or operation source is for AUTO mode. It will return to
AUTO mode whenever power on again after power off. If there is multi-function input terminal
used to switch AUTO / HAND mode, the highest priority is the multi-function input terminal. When
the external terminal is OFF, the drive will not accept any operation signal and cannot execute
JOG.
It is used to set the source of the operation frequency in AUTO mode.
When the operation command is controlled by the keypad KPC-CC01 (optional), keys RUN,
STOP and JOG (F1) are valid.
The parameter determines how the motor is stopped when the drive receives stop command.
1. Ramp to stop: the AC motor drive decelerates to 0 or minimum output frequency (Pr. 01-09)
CALL NOW 800-985-6929
http://www.deltaacdrives.com
Source of the Operation Command (AUTO)
Settings
0: Digital keypad
1: External terminals
2: Communication RS-485 input
3: CANopen communication card
5: Communication card (not includes CANopen card)
[Note]:Need to use with MO setting as 42, or use with KPC-CC01
Stop Method
Settings
0: Ramp to stop
1: Coast to stop
according to current set deceleration time and then stop (by Pr. 01-07).