Source Of The Operation Command (Auto); Stop Method - Delta MS300 Series User Manual

Standard compact drive
Hide thumbs Also See for MS300 Series:
Table of Contents

Advertisement

CALL NOW 800-985-6929
 The AUTO / HAND mode can be switched by the keypad KPC-CC01 (optional) or multi-function
input terminal (MI) to set the source of the master frequency.
 Pr. 00-20 and Pr. 00-21 are for the settings of frequency source and operation source in AUTO
mode. Pr. 00-30 and Pr. 00-31 are for the settings of frequency source and operation source in
HAND mode.
 The factory setting of frequency source or operation source is for AUTO mode. It will return to
AUTO mode whenever power on again after power off. If there is multi-function input terminal
used to switch AUTO / HAND mode, the highest priority is the multi-function input terminal. When
the external terminal is OFF, the drive will not accept any operation signal and cannot execute
JOG.
 It is used to set the source of the operation frequency in AUTO mode.
 When the operation command is controlled by the keypad KPC-CC01 (optional), keys RUN,
STOP and JOG (F1) are valid.
 The parameter determines how the motor is stopped when the drive receives stop command.
1. Ramp to stop: the AC motor drive decelerates to 0 or minimum output frequency (Pr. 01-09)
CALL NOW 800-985-6929
http://www.deltaacdrives.com

Source of the Operation Command (AUTO)

Settings
0: Digital keypad
1: External terminals
2: Communication RS-485 input
3: CANopen communication card
5: Communication card (not includes CANopen card)
[Note]:Need to use with MO setting as 42, or use with KPC-CC01

Stop Method

Settings
0: Ramp to stop
1: Coast to stop
according to current set deceleration time and then stop (by Pr. 01-07).
http://www.deltaacdrives.com
Chapter 12 Description of Parameter SettingsMS300
12-00-9
Email: info@deltaacdrives.com
Factory Setting: 0
Factory Setting: 0