Proportional Gain (P); Integral Time (I); Derivative Time (D) - Delta MS300 Series User Manual

Standard compact drive
Hide thumbs Also See for MS300 Series:
Table of Contents

Advertisement

CALL NOW 800-985-6929
 Pr. 00-21 = 0 to operate from the digital keypad
 Pr. 00-20 = 0, the set point is controlled by the digital keypad
 Pr. 08-00 = 1 (Negative PID feedback from analog input)
 ACI analog input Pr. 03-01 set to 5, PID feedback signal.
 Pr. 08-01-08-03 will be set as required
If there is no vibration in the system, increase Pr. 08-01 (Proportional Gain (P))
If there is no vibration in the system, reduce Pr. 08-02 (Integral Time (I))
If there is no vibration in the system, increase Pr. 08-03 (Differential Time (D))
 Refer to Pr. 08-00 to 08-21 for PID parameters settings.
 When the setting is 1.0, it means Kp gain is 100 %; setting is 0.5, Kp gain means 50 %.
 It is used to eliminate the system error. It is usually used to decrease the error and get the faster
response speed. But if the value is set too high, it may cause the system oscillation and
instability.
 If the other two gains (I and D) are set to zero, proportional control is the only one effective.
 The integral controller is used to eliminate the error during stable system. The integral control
doesn't stop working until error is 0. The integral is acted by the integral time. The smaller
integral time is set, the stronger integral action will be. It is helpful to reduce overshoot and
oscillation to make a stable system. At this moment, the decreasing error will be slow. The
integral control is often used with other two controls to become PI controller or PID controller.
 This parameter is used to set the integral time of I controller. When the integral time is long, it will
have small gain of I controller, the slower response and bad external control. When the integral
time is short, it will have large gain of I controller, the faster response and rapid external control.
 When the integral time is too small, it may cause system oscillation.
 If the integral time is set as 0.00, Pr. 08-02 will be disabled.
 The differential controller is used to show the change of system error and it is helpful to preview
the change of error. So the differential controller can be used to eliminate the error to improve
system state. With the suitable differential time, it can reduce overshoot and shorten adjustment
time. However, the differential operation will increase the noise interference. Please note that
too large differential will cause big noise interference. Besides, the differential shows the change
and the output of the differential will be 0 when there is no change. Therefore, the differential
control can't be used independently. It needs to be used with other two controllers to make a PD
controller or PID controller.
CALL NOW 800-985-6929
http://www.deltaacdrives.com

Proportional Gain (P)

Settings
0.0~500.0

Integral Time (I)

Settings
0.00~100.00 sec.

Derivative Time (D)

Settings
0.00~1.00 sec.
http://www.deltaacdrives.com
Chapter 12 Description of Parameter SettingsMS300
12.1-08-3
Email: info@deltaacdrives.com
Factory Setting: 1.0
Factory Setting: 1.00
Factory Setting: 0.00
Email: info@deltaacdrives.com