 For example, if we set the parameter to 10.00 sec. , when PID target value change from 0 % to
100 %, it needs to take 10 sec. for PID command from 0 % to 100 %; the same situation when
target value change from 100 % to 0 %, it also needs to take 10 sec. for PID command from
100 % to 0 %.
 This parameter is valid when auxiliary and master frequency function opens.
When Pr. 08-29 = 0, PID control output 100.00 % corresponding to the max. output frequency;
When Pr. 08-29 = 1, PID control output 100.00 % corresponding to the input value of auxiliary
frequency (If the auxiliary frequency changes, PID output frequency is also followed changes
together.)
CALL NOW 800-985-6929
http://www.deltaacdrives.com

Selection of frequency base corresponding to 100.00 % PID

Settings
0: PID control output 100.00 % corresponding to max. output frequency
(Pr. 01-00)
1: PID control output 100.00 % corresponding to the input value of auxiliary
frequency
http://www.deltaacdrives.com
Chapter 12 Description of Parameter SettingsMS300
12.1-08-11
Email: info@deltaacdrives.com
Factory Setting:0