Settings
OOB loading balance
82
detection
Multi-motors (IM)
83
selection bit 0
Multi-motors (IM)
84
selection bit 1
These settings are used when multi-function input terminals are set to 19, 20 (UP / DOWN
Command). The frequency increases / decreases according to Pr. 02-09 and Pr. 02-10.
Pr. 11-00 bit 7 = 1, frequency is not saved. The frequency command returns to zero when the
drive stops, and the displayed frequency is 0.00 Hz. The frequency increases / decreases
command by using UP / DOWN key is valid only when the drive is running.
When Pr. 02-09 set to 0: increasing / decreasing frequency command (F) according to the setting
of acceleration / deceleration (Refer to Pr. 01-12~01-19)
Mu lti - fun cti on i np u t ter mi na l 19
fr eq u en cy inc re as ed co mma nd
CALL NOW 800-985-6929
http://www.deltaacdrives.com
Functions
UP / DOWN Key Mode
Settings
0: UP / DOWN by the accel. / decel. time
1: UP / DOWN constant speed (Pr. 02-10)
2: Pulse signal (Pr. 02-10)
3: External terminals UP / DOWN key mode
Constant Speed. the Accel. / Decel. Speed of the UP / DOWN Key
Settings
0.001~1.000 Hz / ms
Fr eq ue n cy
http://www.deltaacdrives.com
Chapter 12 Description of Parameter SettingsMS300
OOB (Out Of Balance Detection) function can be used with
PLC program in washing machine system. When the contact of
this function is ON, receiving ∆θ value by Pr. 07-46 and Pr.
07-47. PLC or higher level controller will decide the operation
speed of motor according to this ∆θ value.
When the contact of this function is ON, parameters can be
changed (Pr. 01.01~01.06, Pr. 01.26~01.43, Pr. 07.18~07.38,
Pr. 07.00~07.06)
Example: MI1 = 27, MI2 = 28
When MI1 OFF, MI2 OFF: motor 1
MI1 ON, MI2 OFF: motor 2
MI1 OFF, MI2 ON: motor 3
MI1 ON, MI1 ON: motor 4
Fr eq ue n cy
co mma nd
Inc re as ed b y ac cel e ra tio n tim e
ON
12.1-02-9
Email: info@deltaacdrives.com
Descriptions
Factory Setting: 0
Factory Setting: 0.001
T ime
OFF