Cable gland
The inverter has 1 cable gland for the communications
cable with 2x2 cable feed-throughs.
Cable requirements
●
Shielded twisted-pair cable (CAT5 or CAT6)
●
Cable diameter: 7.2 / 8.7 / 10.0 mm
●
Wire cross-section: 0.25 ... 1.5 mm
The communications cable is required for connection to
the following units:
●
Power Monitor (part of the Hybrid E5 System, con-
nection is necessary)
●
Power meter (part of the Hybrid E5 System, connec-
tion is necessary)
●
Alarm (external device, connection is optional)
●
Ripple control receiver (external device, connection is
optional)
●
External switch off (external device, connection is
optional)
●
PC
Installation Instructions for the Hybrid E5 Battery Storage System EU V1 EN 2018-09-17
Connect the communication card of the inverter
Overview of communications card
1 Protection against electromagnetic interference (EMI)
2 1 x dry contacts (terminal box)
3 DIP switch for the RS485 termination resistor
4 RS485 (terminal block)
5 Digital inputs and external power-off (terminal block)
RS485 terminal block
2
1
2
3
4
5
6
The connections for RS485, the digital
inputs, the dry contacts and the external
power-off (EPO) are all on the communica-
tion card. This means that the installation
work can be combined.
1
2
5
VCC (+24 V; ≤ 0.8 A)
GND
DATA+ (RS485)
DATA– (RS485)
DATA+ (RS485)
DATA– (RS485)
Overview
3
4
Voltage supply for Smart
Monitor R4E
Data connection to Smart
Monitor
Data connection to P1E/
P3E power meter