Chapter 12 Description of Parameter SettingsMS300
Settings
Error output selection 2
36
(Pr. 06-24)
Error Output Selection 3
37
(Pr. 06-25)
Error Output Selection 4
38
(Pr. 06-26)
Speed attained
40
(including Stop)
42
Crane function
Motor actual speed
43
output < Pr. 02-47
44
Low current output
UVW magnetic contactor
45
ON / OFF switch
46
Master dEb signal output
CALL NOW 800-985-6929
http://www.deltaacdrives.com
Functions
Active when Pr. 06-24 is ON.
Active when Pr. 06-25 is ON.
Active when Pr. 06-26 is ON.
Active when the output frequency attains to setting frequency or
stop.
This function should be used with Pr. 02-32, Pr. 02-33, Pr. 02-34,
Pr. 02-57 and Pr. 02-58.
Active when setting Pr. 07-16 = Pr.02-34, Fcmd > Pr. 02-34,
output current > Pr. 02-33 and time > Pr. 02-32; multi-function
output setting = 42 crane function.
The example of the crane application is as follows for your
reference.
Active when motor actual speed is less than Pr. 02-47.
This function is used with Pr. 06-71 ~ Pr. 06-73.
Use this function with external terminal input = 49 (drive enabled) and
external terminal output = 45 (electromagnetic contractor enabled),
then the magnetic contactor will be ON or OFF according to the
status of drive.
When dEb arises at Master, MO will send a dEb signal to Slave.
Output the message when dEb occurs to Master. This will ensure
that dEb also occurs to Slave. Then Slave will follow the
decelerate time of Master to stop simultaneously.
http://www.deltaacdrives.com
Descriptions
En abl e
C onta cto r
AC Drive
U (T1 )
V(T2 )
W(T3 )
MOx=45
12.1-02-14
Email: info@deltaacdrives.com
MC
Mo to r
IM
3 ~
MIx=49