Chapter 12 Description of Parameter SettingsMS300
Once output speed (frequency) reaches desired speed (frequency), if the corresponding
multi-function output terminal is set to 3 ~ 4 (Pr. 02-13, Pr. 02-36, and Pr. 02-37), this
multi-function output terminal will be "closed".
When output frequency is ≥ Pr. 02-34 (actual output H ≥ 02-34), the multi-function terminal
(Pr. 02-13, 02-16, 02-17) be set to 29 will activate.
When output frequency is < Pr. 02-34 (actual output H < 02-34), the multi-function terminal
(Pr. 02-13, 02-16, 02-17) be set to 30 will activate.
Set value is 1:
Status 1: After the drive is powered on and the external terminal for RUN keeps ON, the drive will
Status 2: After clearing fault once a fault is detected and the external terminal for RUN keeps ON,
the drive can run after pressing RESET key.
This parameter should be used with the multi-function output terminals set to 43. Required to be
used with PG cared and motor with encoder feedback.
CALL NOW 800-985-6929
http://www.deltaacdrives.com
The Width of the Desired Frequency Attained 2
Settings
0.00~599.00 Hz
H
Fcmd=60Hz
02-24=40Hz
02-25=2Hz
02-22=10Hz
02-23=2Hz
02-13,02-14,
=3
02-36,02-37,
02-13,02-14,
02-36,02-37, =4
Output Frequency Setting for Multi-function Output Terminal
Settings
0.00~599.00 Hz
External Operation Control Selection after Reset and Activate
Settings
0: Disable
1: Drive runs if the run command still exists after reset or re-boots.
run.
Zero-speed Level of Motor
Settings
0~65535 rpm
http://www.deltaacdrives.com
12.1-02-18
Email: info@deltaacdrives.com
Factory Setting: 2.00
42Hz
40Hz
38Hz
12Hz
10Hz
8Hz
T
Factory Setting: 0.00
Factory Setting: 0
Factory Setting: 0