Upper differential output
X0~X17
Y0~Y17
-
Upper differential output commands. When X0=Off→On (positive edge-triggered), the
PLS command will be executed, and M0 will send one pulse, with a pulse length
consisting of one scanning period.
Ladder diagram:
X0
M0
PLS
M0
SET
Y0
Time sequence diagram:
X0
Time for one scan cycle
M0
Y0
Lower differential output
X0~X17
Y0~Y17
-
Lower differential output command. When X0= On→Off (negative edge-triggered), the
PLF command will be executed, and M0 will send one pulse, with pulse length
consisting of one scanning period.
Ladder diagram:
X0
M0
PLF
M0
SET
Y0
Time sequence diagram:
X0
Time for one scan cycle
M0
Y0
Program conclusion
An END command must be added to the end of a ladder diagram program or
command program. The PLC will scan from address 0 to the END command, and will
return to address 0 and begins scanning again after execution.
http://www.deltaacdrives.com
Chapter 16 PLC Function ApplicationsMS300
Function
M0~M799
T0~159
-
Command code:
LD
PLS
LD
SET
Function
M0~M799
T0~159
-
Command code:
LD
PLF
LD
SET
Function
N/A
16-43
Email: info@deltaacdrives.com
C0~C79
D0~D399
-
-
Description:
X0
Load Contact A of X0
M0 Upper differential
M0
output
M0
Load Contact A of M0
Y0 Action continues
Y0
(ON)
C0~C79
D0~D399
-
-
Description:
X0
Load Contact A of X0
M0 Lower differential
M0
output
M0
Load Contact A of M0
Y0 Action continues
Y0
(ON)