This parameter is a high frequency injection command in PM SVC control mode, and usually it
doesn't need to be adjusted. But if a motor's rated frequency (i.e. 400 Hz) is too close to the
frequency setting of this parameter (i.e. factory setting 500 Hz), the accuracy of angles detected
will be affected. Therefore, refer to the setting of Pr. 01-01 before adjusting this parameter.
If the setting value of Pr. 00-17 is lower than Pr. 10-51*10, then increase the frequency of carrier
wave.
Pr. 10-51 is valid only when Pr. 10-53 = 2.
The parameter is magnitude command of high frequency injection signal in PM SVC control
mode.
Increasing the parameter can get more accurate estimated value of angle. But the noise of
electromagnetic might be louder if the setting value is too high.
This parameter will be received when motor's parameter is "Auto". And this parameter will
influence the accuracy of angel's estimation.
When the ratio of salient pole (Lq / Ld) is lower, increase Pr. 10-52 to make angle detection be
accurate.
Pr. 10-52 is valid only when Pr. 10-53 = 2.
It is suggested to set as "2" if it is IPM; set as "3" if it is SPM. If there is bad effect when set as
"2" or "3", then set as "1".
CALL NOW 800-985-6929
http://www.deltaacdrives.com
Injection Frequency
Settings
0~1200 Hz
Injection Magnitude
Settings 0.0~200.0 V
Position Detection Method
Settings
0: Disabled
1: Internal 1/4 rated current attracting the rotor to zero degrees
2: High frequency injection
3: Pulse injection
http://www.deltaacdrives.com
Chapter 12 Description of Parameter SettingsMS300
12.1-10-6
Email: info@deltaacdrives.com
Factory Setting: 500
Factory Setting: 15.0 / 30.0