When Pr. 08-18 = 0, the unit of Pr. 08-10 and that of Pr. 08-11 become frequency. The settings
then become to 0 ~ 599.00 Hz.
When Pr. 08-18 = 1, the unit of Pr.08-10 and that of Pr. 08-11 switch to percentage. The settings
then switch to 0~200.00 %.
And the percentage is based on the input command value not the maximum. E.g. If the maximum
value is 100 Kg, the current value is 30 kg, if Pr. 08-11 = 40 %, the value is 12 kg.
Pr. 08-10 is according to the same
When the frequency command is smaller than the sleep frequency and less than the sleep time,
the frequency command is equal to the sleep frequency. However the frequency command
remains at 0.00 Hz until the frequency command becomes equal to or bigger than the wake-up
frequency.
When the PID control function is normal, it should calculate within a period of time and close to
the target value.
Refer to the PID control diagram for details. When executing PID feedback control, if |PID
reference target value – detection value| > Pr. 08-13 PID Deviation Level and exceeds Pr. 08-14
setting, it will be judged as the PID control fault. Multiple-function output MO = 15 (PID feedback
error) will activate.
Pr. 08-16 = 0: PID compensation value is given via Pr. 08-17 setting.
CALL NOW 800-985-6929
http://www.deltaacdrives.com
Wake-up Frequency
Settings
0.00~599.00 Hz
Sleep Time
Settings
0.0~6000.0 sec.
PID Deviation Level
Settings
1.0~50.0 %
PID Deviation Time
Settings
0.1~300.0 sec.
Filter Time for PID Feedback
Settings
0.1~300.0 sec.
PID Compensation Selection
Settings
0: Parameter setting
1: Analog input
http://www.deltaacdrives.com
Chapter 12 Description of Parameter SettingsMS300
logic for calculation
.
12.1-08-7
Email: info@deltaacdrives.com
Factory Setting: 0.00
Factory Setting: 0.0
Factory Setting: 10.0
Factory Setting: 5.0
Factory Setting: 5.0
Factory Setting: 0