Series Circuit Block; Parallel Circuit Block; Read Stack (Pointer Does Not Change) - Delta MS300 Series User Manual

Standard compact drive
Hide thumbs Also See for MS300 Series:
Table of Contents

Advertisement

CALL NOW 800-985-6929
Command
ANB
Operand
Command
ORB
Operand
Command
MPS
Operand
Command
MRD
Operand
CALL NOW 800-985-6929
http://www.deltaacdrives.com

Series circuit block

ANB performs an "AND" operation on the previously saved logic results and the
current cumulative register content.
Ladder diagram:
X0
X1
ANB
X2
X3
Block A
Block B

Parallel circuit block

ORB performs an "OR" operation on the previously saved logic results and the current
cumulative register content.
Ladder diagram:
Block A
X0
X1
X2
X3
Block B
Save to stack
Save current content of cumulative register to the stack. (Add one to stack pointer)

Read stack (pointer does not change)

Reads stack content and saves to cumulative register. (Stack pointer does not
change)
http://www.deltaacdrives.com
Chapter 16 PLC Function ApplicationsMS300
Function
N/A
Command code:
LD
Y1
ORI
LDI
OR
ANB
OUT
Function
N/A
Command code:
LD
Y1
ANI
ORB
LDI
AND
ORB
OUT
Function
N/A
Function
N/A
16-37
Email: info@deltaacdrives.com
Description:
X0
Load Contact A of X0
Establish parallel
X2
connection to contact B
of X2
X1
Load Contact B of X1
Establish parallel
X3
connection to contact A
of X3
Series circuit block
Y1
Drive Y1 coil
Description:
X0
Load Contact A of X0
Establish parallel
X1
connection to contact B
of X1
X2
Load Contact B of X2
Establish parallel
X3
connection to contact A
of X3
Parallel circuit block
Y1
Drive Y1 coil
Email: info@deltaacdrives.com

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents