It is used to set the rated speed of the motor according to motor nameplate.
It is used to set the number of motor poles (must be an even number).
Set up Pr. 01-54 and Pr. 05-66 before setting up Pr. 05-67 to make sure motor operates normally.
The factory setting is 40 % of the motor rated current.
This value should be set according to the rated frequency of the motor as indicated on the motor
nameplate. The factory setting is 90 % of rated current.
Example: The rated current of 7.5 HP (5.5 kW) is 25 A, the factory setting is 22.5 A.
It is used to set rated power of motor 4. Factory setting is the power value of drive.
It is used to set the rated speed of the motor according to motor nameplate.
CALL NOW 800-985-6929
http://www.deltaacdrives.com
Rated Speed of Induction Motor 3 (rpm)
Settings
0~65535
1710 (60 Hz 4 poles); 1410 (50 Hz 4 poles)
Pole Number of Induction Motor 3
Settings
2~20
No-load Current of Induction Motor 3 (A)
Settings
0~ Pr. 05-64 factory setting
Stator Resistance (Rs) of Induction Motor 3
Settings
0~65.535
Full-load Current of Induction Motor 4 (A)
Settings
10~120 % of drive's rated current
The setting range will be 2.5~30 A. (25 × 10 % = 2.5 A and 25 × 120 % = 30 A)
Rated Power of Induction Motor 4 (kW)
Settings
0~655.35 kW
Rated Speed of Induction Motor 4 (rpm)
Settings
0~65535
1710 (60 Hz 4 poles); 1410 (50 Hz 4 poles)
http://www.deltaacdrives.com
Chapter 12 Description of Parameter SettingsMS300
12.1-05-7
Email: info@deltaacdrives.com
Factory Setting: 1710
Factory Setting: 4
Unit: Ampere
Factory Setting: #.##
Factory Setting: #.###
Unit: Ampere
Factory Setting: #.##
Factory Setting: #.##
Factory Setting: 1710