Display
11
12
13
14
15
16
18
21
CALL NOW 800-985-6929
http://www.deltaacdrives.com
DC BUS voltage is less than Pr. 06-00 during acceleration.
Corrective Actions
Check if the input voltage is normal.
Check for possible sudden load.
Check the setting of Pr. 06-00.
DC BUS voltage is less than Pr. 06-00 during deceleration.
Corrective Actions
Check if the input voltage is normal.
Check for possible sudden load.
Check the setting of Pr. 06-00.
DC BUS voltage is less than Pr. 06-00 in constant speed.
Corrective Actions
Check if the input voltage is normal.
Check for possible sudden load.
Check the setting of Pr. 06-00.
DC BUS voltage is less than Pr. 06-00 at stop.
Corrective Actions
Check if the input voltage is normal.
Check for possible sudden load.
Check the setting of Pr. 06-00.
Phase Loss.
Corrective Actions
Check if there is any phase loss in 3-phase model or in 1-phase input
application.
IGBT is over-heated than protection level.
Corrective Actions
Ensure that the ambient temperature falls within the specified
temperature range.
Make sure that the ventilation holes are not obstructed.
Remove any foreign objects from the heat sink and check for possible
dirty in heat sink.
Check the fan and clean it.
Provide enough spacing for adequate ventilation.
IGBT Hardware Error.
Corrective Actions
Return to the factory.
Overload. The AC motor drive detects excessive drive output current.
Corrective Actions
Check if the motor is overloaded.
Take the next higher power AC motor drive model.
http://www.deltaacdrives.com
Chapter 14 Error CodesMS300
Descriptions
14-3