Chapter 12 Description of Parameter SettingsMS300
Must be converted to decimal when using the keypad to set parameters.
Example: If user defined unit is inWG and the third decimal point, according to the information
When Pr. 00-26 is NOT set to 0, the user defined value is enabled. After selecting displayed unit
and decimal point by Pr. 00-25, the setting value of Pr. 00-26 will correspond to Pr. 01-00 (Max.
operation frequency of motor), then the operation frequency of motor will be a linear
correspondence with displayed value of digital keypad.
Example: When the frequency at Pr. 01-00 = 60.00 Hz, the max. user defined value at Pr. 00-26
NOTE
The drive will display as Pr. 00-25 setting when Pr. 00-25 is properly set and Pr. 00-26 is not 0.
Pr. 00-27 will display user defined value when Pr. 00-26 is not set to 0.
User defined value is valid only when Pr. 00-20 (source of frequency) is set to digital keypad or
RS-485 communication.
AUTO / HAND mode can be selected or switched by using digital keypad
(optional)
CALL NOW 800-985-6929
http://www.deltaacdrives.com
above, corresponding to inWG is 01Axh (x is the set decimal point), and
corresponding to the third decimal place is 0003h. Then inWG and the third decimal
point displayed in hexadecimal is 01A3h, converted to decimal is 01A3h = 419.
Set Pr. 00-25 = 419 to complete setting.
Max. User Defined Value
Settings
0: Disable
0~65535 (when Pr. 00-25 set to no decimal place)
0.0~6553.5 (when Pr. 00-25 set to 1 decimal place)
0.0~655.35 (when Pr. 00-25 set to 2 decimal place)
0.0~65.535 (when Pr. 00-25 set to 3 decimal place)
is 100.0 %. That also means Pr. 00-25 is set at 0021h to select % as the unit.
User Defined Value
Settings
Read only
LOCAL / REMOTE Selection
Settings
0: Standard HOA function
1: Switching Local / Remote, the drive stops
2: Switching Local / Remote, the drive runs as the REMOTE setting for
frequency and operation status
3: Switching Local / Remote, the drive runs as the LOCAL setting for
frequency and operation status
4: Switching Local / Remote, the drive runs as LOCAL setting when switch to
Local and runs as REMOTE setting when switch to Remote for frequency
and operation status.
or setting multi-function input terminal MI = 41, 42.
http://www.deltaacdrives.com
12-00-12
Email: info@deltaacdrives.com
Factory Setting: 0
Factory Setting: Read only
Factory Setting: 0