Dyn press superv
sh'down
Dyn superv press diff min
Dyn superv press diff max
Dyn superv press
increase
Dyn press superv time
Dyn press superv tme
const
Building Technologies Division

6.11.22 Dynamic pressure supervision

Line no.
Operating line
2490
Dyn press superv sh'down
Start prevention
Lockout position
Line no.
Operating line
2491
Dyn superv press diff min
Line no.
Operating line
2492
Dyn superv press diff max
Note!
The parameters used for the dynamic water pressure limits are not OSV- (out of
service) compatible. Nevertheless, the individual supervisory functions can be
deactivated by setting parameter Dyn superv press diff min (2491) to 0 bar, or
parameter Dyn superv press diff max (2492) to 5 bar. If all types of pressure
supervision are deactivated, only the respective water pressure is displayed
If only dynamic water pressure supervision is required, static pressure
supervision can be deactivated by setting the parameters for the static water
pressure limits to OSV (out of service). In that case, a plausibility check of the
sensor is not made, which means that sensor faults can no longer be detected
since the test is performed by acquiring the static pressure values
Line no.
Operating line
2494
Dyn superv press increase
No
Yes
Line no.
Operating line
2495
Dyn press superv time
Line no.
Operating line
2496
Dyn press superv tme const
User Manual LMS14...
6 The settings in detail
237/617
CC1U7471en