Info/diagnostics
Additional parameters
350/617
Building Technologies Division
If, during charging, the temperature at sensor B36 (DHW charging temp (8836))
exceeds the charging setpoint by the current Switching diff off min DHW
(2461)/Switching diff off max DHW (2462), the burner is switched off. It is switched on
again as soon as the temperature at sensor B36 drops by the parameterized Switching
diff on DHW (2460) below the charging temperature setpoint. The setting range for the
switch-on differential starts at 0 °C.
The output request to the burner is controlled between the parameterized Required
speed LF min (9525) and the maximum output for Fan speed full charging max (2442).
If, during the time full charging is active, the enable criterion for full charging does not
apply anymore, the DHW request is ended according to the criteria for recharging.
Line no.
Operating line
DHW temp 1
8830
DHW temp setpoint
8831
DHW temp 2
8832
DHW charging temp
8836
Line no.
Operating line
Fan speed full charging max
2442
Switching diff on DHW
2460
Switching diff off min DHW
2461
Switching diff off max DHW
2462
Switching diff
5024
Pump speed min
5101
Intermediate circuit boost
5140
Excess interm circ temp max
5141
Full charging with B36
5146
Required speed LF min
9525
User Manual LMS14...
6 The settings in detail