Operating line
[4483.1]
DV-DHW step size Ph1
Full step
Half step
Quarter-step
Eighth-step
Line no.
Operating line
[4484.1]
DV-DHW step size Ph2
Full step
Half step
Quarter-step
Eighth-step
Line no.
Operating line
[4485.1]
DV-DHW step size Ph3
Full step
Half step
Quarter-step
Eighth-step
This parameters are used to set the step size for one step pulse in the respective
phase.
Full step
One step pulse causes the stepper motor to travel one full step. Note the time required
per step pulse.
Half step
One step pulse causes the stepper motor to travel half a step. Note the time required
per step pulse (2 pulses for one full step).
Quarter-step
One step pulse causes the stepper motor to travel one quarter of a step. Note the time
required per step pulse (4 pulses for one full step).
Eighth-step
One step pulse causes the stepper motor to travel one eighth of a step. Note the time
required per step pulse (8 pulses for one full step).
User Manual LMS14...
6 The settings in detail
387/617