6.11.11 Boiler pump

Line no.
Operating line
2300
FrostPlnt boiler pump
Off
On
This parameter is used to select whether frost protection for the plant shall also act on
the boiler pump.
Off
Frost protection for the plant does not act on the boiler pump.
On
Frost protection for the plant also acts on the boiler pump.
Line no.
Operating line
2301
Boiler pump on heat gen lock
Off
On
This parameter is used to define whether the heat generation lock shall also act on the
boiler pump.
Off
Boiler pump locked when the heat generation lock is active.
On
Boiler pump not locked when the heat generation lock is active.
Warning!
Due to the locked boiler pump in the case of heat generation lock (Boiler pump
on heat gen lock (2301) set to Off), frost protection requests from consumers
cannot be satisfied while heat generation lock is active.
Also, cold water from consumers is prevented from reaching the boiler to
ensure it does not trigger frost protection for the boiler.
It is only frost protection for the boiler called for by sensor B2 that can put the
burner and the boiler pump into operation.
Also refer to chapter Boiler pump, parameter Syst pump on heat gen lock (2121).
Line no.
Operating line
2305
Impact heat generation lock
Heating mode only
Heating and DHW mode
This parameter is used to select whether the heat generation lock shall only be active in
the case of heat requests from the heating circuit, or in the case of DHW heating
requests also.
Heating mode only
Only space heating requests are locked. DHW heating requests continue to be met.
Heating and DHW mode
All space heating and DHW heating requests are locked.
User Manual LMS14...
6 The settings in detail
CC1U7471en
07.05.2014