Sensor type collector
Readjustm collector
sensor
Readjustm outside sensor
Sensor type flue gas temp
Readjustm flue gas sensor
436/617
Building Technologies Division

6.23.19 Types of sensors/readjustments

Line no.
Operating line
6097
Sensor type collector
NTC
Pt1000
If a wider temperature range is required, a sensor with a platinum characteristic
(-28...350 °C) can be used as sensor B6 in place of an NTC sensor
(-28...200 °C). The type of sensor can be selected independent of multifunctional
sensor input BX (basic unit and extension module) at which sensor B6 is set and
connected to. The respective input uses automatically the correct characteristic,
provided it is configured accordingly.
Setting the type of sensor used. The controller uses the respective temperature
characteristic.
Line no.
Operating line
6098
Readjustm collector sensor
The measured value can be readjusted.
Line no.
Operating line
6100
Readjustm outside sensor
The measured value of the outside temperature can be shifted by ±3 K.
Line no.
Operating line
6101
Sensor type flue gas temp
NTC
Pt 1000
NTC 20k
Line no.
Operating line
6102
Readjustm flue gas sensor
The measured value can be readjusted.