Configuration - Siemens LMS14 User Manual

Albatros2 boiler management unit
Table of Contents

Advertisement

Capacity
LP configuration
522/617
Building Technologies Division
6.34.5

Configuration

Line no.
Operating line
9610
Capacity
Up to 70 kW
Up to 120 kW
Above 120 kW
In compliance with the standards, the LMS14... supports 2 capacity ranges:
Up to 70 kW
See up to 120 kW (the LMS14... does not differentiate).
Up to 120 kW
Capacity range up to 120 kW (see sequence diagram for burner capacities <120 kW).
Above 120 kW
Capacity range above 120 kW (see sequence diagram for burner capacities >120 kW.
Line no.
Operating line
9611
LP configuration
LP mode 1
LP mode 2
LP mode 3
LP mode 4
LP mode 5
Configuration of input for air pressure switch:
LP mode 1
No monitoring by air pressure switch (input can be used for some other function).
LP mode 2
Monitoring by air pressure switch from phase TV to phase TVZ.
LP mode 3
Monitoring by air pressure switch in phase TV.
LP mode 4
Monitoring by air pressure switch in phases TW1, TW2 and TVZ.
LP mode 5
Monitoring by air pressure switch during Standby.
Warning!
Here, the safety-related setting for input H7 is made. Function input H7 (6011)
is of importance only if this parameter is set to LP mode 1.
If, with this safety-related parameter, a function other than LP mode 1 is
selected, Function input H7 (6011) only accepts None.
User Manual LMS14...
6 The settings in detail
CC1U7471en