Calculation
Key
Heating curve
displacement
Key
Building Technologies Division
The resulting flow temperature can be calculated as follows:
TV = TR + [ 2 + (TR - TAgem) - 0.005 * (TR - TAgem)2 ] * s
The impact of compensation variant Weather compensation with room influence on the
flow temperature setpoint is calculated as follows:
TV = TRw * (1 + s)
Line no.
Meaning
TV
Resulting flow temperature adaption
TRw
Room temperature setpoint readjustment (due to room influence)
TV
Flow temperature setpoint heating circuit
TR
Room temperature setpoint – heat gains + room influence
TAgem
Composite outside temperature
s
Heating curve slope
Line no.
HC1
HC2
HC3
721
1021
1321
Parallel displacement of the heating curve is used to change the flow temperature
evenly across the entire outside temperature range or, in other words, if the room
temperature is always too high or too low, a readjustment must be made via parallel
displacement.
TV
°C
100
90
80
70
60
50
40
30
30
20
10
10
10
0
Figure 18: Heating curve – heating curve displacement
Line no.
Meaning
8700
TA
Outside temperature
TRw
Room temperature setpoint
TV
Flow temperature
User Manual LMS14...
6 The settings in detail
Operating line
Heating curve displacement
0
-10
-20
0
-30
°C
8700
7471d48/0910
CC1U7471en
07.05.2014
137/617