Siemens LMS14 User Manual page 523

Albatros2 boiler management unit
Table of Contents

Advertisement

GP configuration
Home run mode
Postpurging level
Building Technologies Division
Line no.
Operating line
9612
GP configuration
GP not connected
GP connected
Configuration of input for gas pressure switch:
GP not connected
No monitoring by gas pressure switch (input can be used for some other function).
GP connected
Monitoring by gas pressure switch (see sequence diagram).
Warning!
Here, the safety-related setting for input H6 is made. Parameter Function input
H6 (6008) is of importance only when set to GP not connected.
If, with this safety-related parameter, function GP connected is selected,
parameter Function input H6 (6008) only accepts None.
Line no.
Operating line
9613
Home run mode
Start with HomeRun
Start without HomeRun
Selection of Postpurging mode.
Startup with HomeRun
At the end of postpurging TN2, the change to home run is always made.
Startup without HomeRun
Direct startup from postpurging TN2 possible (interruptable postpurging).
Line no.
Operating line
9614
Postpurging level
Run
Prepurge
Selection of postpurging level at the end of the operating phase.
Run
Postpurging based on last operational control.
Prepurge
Postpurging at prepurge speed.
User Manual LMS14...
6 The settings in detail
523/617
CC1U7471en
28.01.2015