6.5.8

Flow temperature setpoint limits

Line no.
HC1
HC2
HC3
740
1040
1340
741
1041
1341
Using this limitation, a temperature range for the flow temperature setpoint can be
defined. If the flow temperature setpoint called for by the heating circuit reaches the
relevant limit and the request for heat increases or decreases, the flow temperature
setpoint is maintained at the maximum or minimum limit.
TV
Max.
Act.
740 / 1040 / 1340
Min.
0
10
20
Figure 21: Flow temperature setpoint limits
Line no.
HC1
HC2
HC3
740
1040
1340
741
1041
1341
8744
8774
8803
The calculated flow temperature setpoint is limited according to the setting made. The
limitation is active in all operating modes. Even forced signals cannot push the flow
temperature setpoint above that level.
Warning!
Maximum limitation is not a safety function. If the flow temperature exceeds this
limit, the heating circuit pump will not be deactivated.
The flow temperature setpoint is limited according to the setting made. This also applies
to heat requests made to the heat sources.
User Manual LMS14...
6 The settings in detail
Operating line
Flow temp setpoint min
Flow temp setpoint max
8744 / 8774 / 8803
30
40
50
60
Meaning
TVmin
Minimum flow temperature setpoint
TVmax
Maximum flow temperature setpoint
TVw
Flow temperature setpoint 1/2/3
741
1041
1341
°C
70
80
90
100
CC1U7471en
07.05.2014