6.11.6 PID control algorithm

To parameterize the PID control algorithm, 2 sets of controller coefficients are available.
One set is used for Heating mode, the other for drawing DHW from the instantaneous
water heater or for charging a DHW storage tank (DHW).
Control parameters for Heating mode:
Line no.
Operating line
2233
P-band Xp HCs
2234
Int action time Tn HCs
2235
Der action time Tv HCs
Control parameters for DHW mode:
Line no.
Operating line
2236
P-band Xp DHW
2237
Int action time Tn DHW
2238
Der action time Tv DHW
Line no.
Operating line
2233
P-band Xp HCs
2236
P-band Xp DHW
P-band Xp defines the controller's gain. A small Xp leads to higher burner fan speeds
without changing the control offset T = (temperature setpoint – actual value of
temperature).
Line no.
Operating line
2234
Int action time Tn HCs
2237
Int action time Tn DHW
The integral action time Tn defines the controller's rate of response when correcting
proportional offsets. A shorter Tn leads to faster correcting actions.
Line no.
Operating line
2235
Der action time Tv HCs
2238
Der action time Tv DHW
The derivative action time Tv determines the extent of after-effect of a spontaneous
change of control offset. A short Tv only has a short-time impact on the manipulated
variable.