Key
Building Technologies Division
6.38 Fan parameters settable as load values via
QAA75.../AVS37...
Under certain conditions, the fan parameters for ignition load, low-fire, high-fire, pre-
and postpurging can also be set via the QAA75.../AVS37...
Since these fan parameters lie within the safety-related area and, basically, safety-
related values cannot be changed via the QAA75.../AVS37..., following applies:
The respective parameters are copied and the new parameters filed in the non-safety-
must fulfill the following conditions
related area and
Line no. QAA75...
Required speed prepurging (9504) ≥
Required speed ignition (9512) ≤
Required speed LF (9524) ≥
Required speed HF (9529) ≥ ≤
Prepurge time (9500) ≥
Postpurge time (9540) ≥
Line no.
Meaning
9504
N_Vor_QAA
Speed required for prepurging (QAA)
9505
N_Vor
Minimum speed required for prepurging
9512
N_ZL_QAA
Speed required for ignition
9513
N_ZL
Maximum speed required for ignition
9524
N_TL_QAA
Speed required for low-fire
9525
N_TL
Minimum speed required low-fire
9529
N_VL_QAA
Speed required for high-fire
9530
N_VL
Maximum speed required for high-fire
9500
Tv_QAA
Prepurge time
9501
Tv
Prepurge time minimum
9540
Tn_QAA
Postpurge time
9542
Tn
Postpurge time minimum
9551
Maximum fan speed stop
9616
Maximum speed
The change between the 2 parameter groups can be parameterized via a safety-related
flag Release QAA fan param [4337.1]
= Off (QAA setting parameters not enabled)
= On (QAA setting parameters enabled)
User Manual LMS14...
6 The settings in detail
:
Safety-related parameters
Req speed prepurging min (9505)
Required speed ignition max (9513)
Required speed LF min (9525)
Required speed HF max 9530)
Prepurge time min (9501)
Postpurge time min (9542)
559/617
CC1U7471en
28.01.2015