Siemens LMS14 User Manual page 51

Albatros2 boiler management unit
Table of Contents

Advertisement

Operator unit
1156
Floor curing day current
1161
Excess heat draw
Off ¦ Heating mode ¦ Always
1170
With buffer
No ¦ Yes
1172
With prim contr/system pump
No ¦ Yes
1180
Pump speed reduction
Operating level ¦ Characteristic ¦ Temp differential
nomial
1181
Starting speed
1182
Pump speed min
1183
Pump speed max
1185
Pump speed min OEM
1186
Pump speed max OEM
1188
Curve readj at 50% speed
1189
Filter time constant speed ctrl
1190
Flow setp readj speed ctrl
No ¦ Yes
1198
Operating level changeover
Frost protection ¦ Reduced ¦ Comfort
1200
Optg mode changeover
None ¦ Protection ¦ Reduced¦ Comfort ¦ Automatic
[4291.2]
Heating circuit 3
1300
Building Technologies Division
Operating line
ACS420
FloorPlastrDryUpDay 2
Overtemp drop HC2
Off ¦ Heating mode ¦ Always
HC2 With buffer
No ¦ Yes
HC2 precontr/PrimPump
No ¦ Yes
Pump speed red HC2
According HC operating level ¦ According
characteristic curve ¦ Temp differential
nominal
Starting speed HC2
Pump speed min HC2
Pump speed max HC2
Pump speed minOEMHC2
Pump speed maxOEMHC2
CurveReadj50%SpeedHC2
FilterTimeSpeCtrlHC2
FlowReadjSpeedCtr HC2
No ¦ Yes
OptgLevelChangeoverHC2
Frost protection ¦ Reduced ¦ Comfort
OptgMode Ch'over HC 2
None ¦ Protection ¦ Reduced¦ Comfort ¦
Automatic
Delay speed contr HC2
Operating mode HC3/P
Protection ¦ Automatic ¦ Reduced ¦ Comfort
User Manual LMS14...
5 Handling
ACS700/ACS790
dry up HC2
Flooring plaster dry up day HC2
Overtemperature drop heating
circuit 2
Off ¦ Heating mode ¦ Always
Heating circuit 2 with buffer
No ¦ Yes
Heating circuit 2 with
precontr/primary pump
No ¦ Yes
Pump speed reduction heating
circuit 2
According HC operating level ¦ According
characteristic curve ¦ Temp differential
nominal
Starting speed HC2
Pump speed min heating circuit 2
Pump speed max heating circuit 2
Pump speed min OEM heating
circuit 2
Pump speed max OEM HC2
Curve readj at 50% speed HC2
Filter time const speed ctrl HC2
Flow setp readj speed ctrl HC2
No ¦ Yes
Operating level changeover HC2
Frost protection ¦ Reduced ¦ Comfort
Operating mode changeover
heating circuit 2
None ¦ Protection ¦ Reduced¦ Comfort ¦
Automatic
Delay speed control HC2
Operating mode HC3/P
Protection ¦ Automatic ¦ Reduced ¦ Comfort
0
32
Always
Yes
Yes
According
characteristic curve
100
0
100
50
BZ 1185
BZ 1183
100
BZ 1182
BZ 1186
50
0
BZ 1182
100
BZ 1183
100
33
0
100
5
0
20
Yes
Reduced
Protection
5
- - -/0
60
Automatic
CC1U7471en
°C
-
%
%
%
%
%
%
Min.
Min.
-
51/617