Sensor selection for the DHW storage tank
Sensor selection for the buffer storage tank
Building Technologies Division

6.15.2 Sensors

In addition to sensor B6, sensor B31 at the bottom is used for solar charging control. If
that sensor is not available, sensor B3 at the top is automatically used. If both storage
tank sensors are not available and the solar diagram is active, an error message is
delivered and the collector pump deactivated, irrespective of collector temperature.
Sensor connected to ... Sensors used for solar charging control
B3
B31
--
--
Sensors
Sensors
--
-- no sensor connected
 with or without sensor or thermostat)
Note!
If both storage tank sensors are not available (short-circuit or interruption), the
collector pump is deactivated. If the collector sensor is not available (short-circuit or
interruption), the collector pump is switched off also. In both cases, an error message
is displayed.
In addition to sensor B6, sensor B41 at the bottom is used for solar charging control. If
that sensor is not available, sensor B4 at the top is automatically used. If both storage
tank sensors are not available and the solar diagram is active, an error message is
delivered and the collector pump deactivated, irrespective of collector temperature.
Sensor connected to
...
B4
B41
--
--
Sensors
Sensors
--
-- no sensor connected
 with or without sensor
Note!
If both storage tank sensors are not available (short-circuit or interruption), the
collector pump is deactivated. If the collector sensor is not available (short-circuit or
interruption), the collector pump is switched off as well. In both cases, an error
message is displayed.
User Manual LMS14...
6 The settings in detail
Solar DHW heating not possible
Sensor B6  collector temperature
Sensor B31 at the bottom  storage tank temperature
Sensor B6  collector temperature
Sensor B3 at the top  storage tank temperature
Sensors used for solar charging control
Solar buffer storage tank charging not possible
Sensor B6  collector temperature
Sensor B41 at the bottom  storage tank temperature
Sensor B6  collector temperature
Sensor B4 at the top  storage tank temperature
277/617