Thermal Overload Protection; Monitor Start Protection; Start-Up Supervision; Trip Coil Monitor - Siemens SIPROTEC4 7SJ61 Manual

Communication module
Hide thumbs Also See for SIPROTEC4 7SJ61:
Table of Contents

Advertisement

Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Name
251
>49 O/L BLOCK
252
>EmergencyStart
253
49 O / L OFF
254
49 O/L BLOCK
255
49 O/L ACTIVE
256
49 O/L I Alarm
257
49 O/L \16 Alarm
258
49 Windings O/L
259
49 Th O/L TRIP
260
>66 emer. start
261
66 OFF
262
66 BLOCKED
263
66 ACTIVE
264
66 TRIP
265
START-SUP OFF
266
START-SUP BLK
267
START-SUP ACT
268
START-SUP TRIP
269
Rotor locked
270
START-SUP pu
271
74TC BLOCKED
272
74TC ACTIVE
273
>74TC trip rel.
274
>74TC brk rel.
275
74TC OFF
276
74 ProgFail
277
FAIL: Trip cir.
7SJ61/62/63 6MD63 DNP3.0 Device Profile Document
C53000-L1840-A001-01

Thermal overload protection

>BLOCK 49 Overload Protection; ON = 1, OFF = 0
>Emergency start of motors; ON = 1, OFF = 0
49 Overload Protection is OFF; ON = 1, OFF = 0
49 Overload Protection is BLOCKED; ON = 1, OFF = 0
49 Overload Protection is ACTIVE; ON = 1, OFF = 0
Overload Current Alarm (I alarm); ON = 1, OFF = 0
49 Overload Alarm! Near Thermal Trip; ON = 1, OFF = 0
49 Winding Overload; ON = 1, OFF = 0
49 Thermal Overload TRIP; ON = 1, OFF = 0

Monitor start protection

>Emergency start; ON = 1, OFF = 0
66 Motor start protection OFF; ON = 1, OFF = 0
66 Motor start protection BLOCKED; ON = 1, OFF = 0
66 Motor start protection ACTIVE; ON = 1, OFF = 0
66 Motor start protection TRIP; ON = 1, OFF = 0

Start-up supervision

Startup supervision is OFF; ON = 1, OFF = 0
Startup supervision is BLOCKED; ON = 1, OFF = 0
Startup supervision is ACTIVE; ON = 1, OFF = 0
Startup supervision TRIP; ON = 1, OFF = 0
Rotor locked; ON = 1, OFF = 0
Startup supervision Pickup; ON = 1, OFF = 0

Trip coil monitor

74TC Trip circuit supervision is BLOCKED; ON = 1, OFF = 0
74TC Trip circuit supervision is ACTIVE; ON = 1, OFF = 0
>74TC Trip circuit superv.: trip relay; ON = 1, OFF = 0
>74TC Trip circuit superv.: bkr relay; ON = 1, OFF = 0
74TC Trip circuit supervision OFF; ON = 1, OFF = 0
74TC blocked. Bin. input is not set; ON = 1, OFF = 0
74TCFailure Trip Circuit; ON = 1, OFF = 0
Description
DNP V3.00 Device Profile
1503
3
1507
3
1511
3
1512
3
1513
3
1515
1
1516
1
1517
3
1521
2
4823
3
4824
3
4825
3
4826
3
4827
2
6811
3
6812
3
6813
3
6821
2
6822
1
6823
2
6862
3
6863
3
6852
3
6853
3
6861
3
6864
3
6865
1
3-15