Starting speed
Pump speed min
Pump speed max
Pump speed min OEM
Pump speed max OEM
Curve readj at
50% speed
172/617
Building Technologies Division
Note!
This modulation mode is not suitable for cascade applications.
Note!
To ensure effective control of the heating circuit pump in line with the nominal
increase, limitation of the boiler temperature differential must be deactivated (set
Temp differential max (2316) to OSV).
Note!
When manual control ends, the pump is switched off briefly during the transition to
pump overrun.
Consequently, the heating circuit pump should only be set to the Temp differential
nominal modulation mode if the overtemperature protection function has been
deactivated for the heating circuit concerned.
Line no.
HC1
HC2
HC3
881
1181
1481
The speed of the heating circuit pump for the start kick can be defined here.
Line no.
HC1
HC2
HC3
882
1182
1482
The minimum speed of the heating circuit pump can be defined here.
Line no.
HC1
HC2
HC3
883
1183
1483
The maximum speed of the heating circuit pump can be defined here.
Line no.
HC1
HC2
HC3
885
1185
1485
The minimum speed of the heating circuit pump can be defined here.
Line no.
HC1
HC2
HC3
886
1186
1486
The maximum speed of the heating circuit pump can be defined here.
Line no.
HC1
HC2
HC3
888
1188
1488
Readjustment of the flow temperature setpoint when the pump speed is reduced by
50%. This readjustment is calculated based on the differential of flow temperature
setpoint according to the heating curve and current room temperature setpoint.
User Manual LMS14...
6 The settings in detail
Operating line
Starting speed
Operating line
Pump speed min
Operating line
Pump speed max
Operating line
Pump speed min OEM
Operating line
Pump speed max OEM
Operating line
Curve readj at 50% speed
CC1U7471en