Water Pressure Sensor - Siemens LMS14 User Manual

Albatros2 boiler management unit
Table of Contents

Advertisement

Additional parameters
Building Technologies Division
6.11.23

Water pressure sensor

The pressure sensor for static or dynamic pressure supervision must be configured at
one of the inputs H.
Due to the special requirements placed on the read in and filter algorithms, the
pressure sensor for dynamic pressure measurements must always be configured at
one of the local terminals of the LMS14... (H1/H3). Otherwise, the pressure sensor is to
be configured the same way as it is for static pressure measurements.
Plausibility check of the sensor:
If a configuration with water pressure sensor was selected, the LMS14... must read in a
valid value for the water pressure.
The kind of response to the fault depends on the check of the static water pressure.
Caution!
If all types of static pressure supervision are deactivated via the OSV function,
dynamic pressure supervision remains activated. In that case, a plausibility
check of the sensor will not be made, which means that sensor faults can no
longer be detected since the test is performed by acquiring the static pressure
values.
The water pressure sensor makes possible the following functions:
 Display of water pressure
 Triggering start prevention in case of under- or overpressure
 Water filling
 Water circulation
Line no.
Operating line
5950
Function input H1
5953
Voltage value 1 H1
5954
Function value 1 H1
5955
Voltage value 2 H1
5956
Function value 2 H1
5960
Function input H3
5963
Voltage value 1 H3
5964
Function value 1 H3
5965
Voltage value 2 H3
5966
Function value 2 H3
6046
Function input H2 module 1
6049
Voltage value 1 H2 module 1
6050
Funct value 1 H2 module 1
6051
Voltage value 2 H2 module 1
6052
Funct value 2 H2 module 1
6054
Function input H2 module 2
6057
Voltage value 1 H2 module 2
6058
Funct value 1 H2 module 2
6059
Voltage value 2 H2 module 2
6060
Funct value 2 H2 module 2
6062
Function input H2 module 3
6065
Voltage value 1 H2 module 3
6066
Funct value 1 H2 module 3
6067
Voltage value 2 H2 module 3
6068
Funct value 2 H2 module 3
User Manual LMS14...
6 The settings in detail
241/617
CC1U7471en
07.05.2014

Advertisement

Table of Contents
loading

Table of Contents