Postpurge time
Postpurge time
TL max
Postpurge time min
Postpurge time 2
Postpurging in lockout pos
Required speed
stop max
Building Technologies Division
6.34.4

Postpurging

Line no.
Operating line
9540
Postpurge time
Duration of postpurging, which can be adjusted via the operator terminal. It can only be
set to a value above the Postpurge time min (9542).
Line no.
Operating line
9541
Postpurge time TL max
Duration of postpurge time after a temperature limiter/safety limit thermostat has
responded (safety-related).
Line no.
Operating line
9542
Postpurge time min
Duration of postpurging (safety-related). Limit value for the postpurge time which can
be adjusted via the operator terminal.
Line no.
Operating line
9544
Postpurge time 2
Duration of postpurging that can be interrupted. To be activated via Home run mode
(9613).
Line no.
Operating line
9545
Postpurging in lockout pos
If – when the burner is started – no flame can be established after the permitted
number of repetitions, the phase sequence of the burner control goes to lockout
(Albatros code 133).
Off
No postpurging is performed during the transition to the lockout position.
On
During the transition to the lockout position, postpurging at the prepurge speed is
activated. The duration of the postpurging process is calculated by adding together the
Postpurge time min (9542) and Postpurge time 2 (9544).
Line no.
Operating line
9551
Required speed stop max
Speed from which the current speed is set to 0 (safety-related). When changing to
Standby, the current speed must be lower than this speed.