6.11.15 Output data
Line no.
Operating line
2330
Output nominal
Line no.
Operating line
2331
Output basic stage
These settings are required when several boilers with different capacities operate in a
cascaded system.
Line no.
Operating line
2334
Output at pump speed min
If option Pump modulation (2320) is selected, the boiler pump is operated at minimum
speed until the burner output set on Output at pump speed min (2334) is reached, and
at maximum speed from the burner output set on Output at pump speed max (2335).
If the burner's output lies between these 2 values, the boiler pump's speed is calculated
through linear conversion.
Line no.
Operating line
2335
Output at pump speed max
If option Pump modulation (2320) is selected, the boiler pump is operated at minimum
speed until the burner output set on Output at pump speed min (2334) is reached, and
at maximum speed from the burner output set on Output at pump speed max (2335).
If the burner's output lies between these 2 values, the boiler pump's speed is calculated
through linear conversion.