Output Data - Siemens LMS14 User Manual

Albatros2 boiler management unit
Table of Contents

Advertisement

Output nominal
Output basic stage
Output at pump speed min
Output at pump speed
max
220/617
Building Technologies Division

6.11.15 Output data

Line no.
Operating line
2330
Output nominal
Line no.
Operating line
2331
Output basic stage
These settings are required when several boilers with different capacities operate in a
cascaded system.
Line no.
Operating line
2334
Output at pump speed min
If option Pump modulation (2320) is selected, the boiler pump is operated at minimum
speed until the burner output set on Output at pump speed min (2334) is reached, and
at maximum speed from the burner output set on Output at pump speed max (2335).
If the burner's output lies between these 2 values, the boiler pump's speed is calculated
through linear conversion.
Line no.
Operating line
2335
Output at pump speed max
If option Pump modulation (2320) is selected, the boiler pump is operated at minimum
speed until the burner output set on Output at pump speed min (2334) is reached, and
at maximum speed from the burner output set on Output at pump speed max (2335).
If the burner's output lies between these 2 values, the boiler pump's speed is calculated
through linear conversion.
User Manual LMS14...
6 The settings in detail
CC1U7471en
07.05.2014

Advertisement

Table of Contents
loading

Table of Contents