Holidays - Siemens LMS14 User Manual

Albatros2 boiler management unit
Table of Contents

Advertisement

Preselection
Start
End
Operating level
Building Technologies Division

6.4 Holidays

Line no.
HC1
HC2
HC3
641
651
661
Line no.
HC1
HC2
HC1
642
652
662
Line no.
HC1
HC2
HC1
643
653
663
Line no.
HC1
HC2
HC1
648
658
668
The holiday program enables holiday periods to be preprogrammed for a full calendar
year. When a holiday period is active, the operating level switches to Reduced or Frost
protection (selectable).
Note!
The holiday program can only be used in Automatic operation.
Holiday periods are only active in Automatic operation. In the other operating modes,
they are started and run in the background to become active whenever Automatic
operation is selected.
When a holiday period has elapsed, the controller automatically deletes it. The same
holiday period the following year would have to be reprogrammed.
A holiday period starts at 0:00 of the first day and ends/is deleted at 24:00 of the last
day of the holiday period.
An active holiday period is indicated by the suitcase symbol. The heating circuit's
operating mode does not change.
It is possible to enter a holiday period with the date of the first and last day of the period
(dd.mm). The operating level that shall apply during active holiday periods can be
selected (Reduced or Protection).
The impact of a currently active holiday period can only be canceled by switching to
non-automatic operation or by deleting the programmed holiday period.
User Manual LMS14...
6 The settings in detail
Operating line
Preselection
Period 1
Period 2
Period 3
Period 4
Period 5
Period 6
Period 7
Period 8
Operating line
Start
Operating line
End
Operating line
Operating level
Frost protection
Reduced
129/617
CC1U7471en
07.05.2014