Siemens LMS14 User Manual page 213

Albatros2 boiler management unit
Table of Contents

Advertisement

Key
Temp differential max
Temp differential
nominal
Building Technologies Division
Line no.
HC1
HC2
HC3
889
1189
1489
Line no.
Operating line
2316
Temp differential max
2317
Temp differential nominal
PWM-Min
Parameterized minimum speed of heating circuit or boiler pump
PWM-Max
Parameterized maximum speed of heating circuit or boiler pump
Limitation of the boiler temperature increase in connection with a speed-controlled
pump (heating circuit or boiler pump) is only active in space heating mode. It is
deactivated as soon as there a request for DHW heating.
Prerequisite for limitation of the boiler's temperature differential is a correctly working
sensor B7 and a parameterized upper limit for the permitted boiler temperature
differential: Temp differential max.
Line no.
Operating line
2316
Temp differential max
The maximum boiler temperature differential in connection with a speed-controlled
heating circuit pump is maintained when the pump is controlled at the maximum
permissible speed.
The function can be deactivated by setting OSV (---).
Line no.
Operating line
2317
Temp differential nominal
In connection with a speed-controlled heating circuit pump and pure Heating mode, the
nominal boiler temperature differential is maintained as long as the heating circuit pump
is not controlled at the maximum permissible speed.
User Manual LMS14...