Building Technologies Division
If the Legionella function is pending, it will be performed when DHW heating is released
for the first time in the morning.
When DHW heating is Off, the Frost Protection setpoint applies.
Example:
0
5 6
Figure 33: DHW release – time programs HCs
Time program 4/DHW
When using this setting, a specific time program is available for DHW heating. For
every weekday, a time program with a maximum of 3 on phases can be set. During the
release time, the Nominal DHW setpoint applies, outside the release time, the Reduced
DHW setpoint.
If the Legionella function is pending, it will be performed when DHW heating is released
for the first time in the morning. Setting Once/day or Several times/day has no impact.
When DHW heating is Off, the Frost Protection setpoint applies.
Example:
0
Figure 34: DHW release – time program 4/DHW
User Manual LMS14...
6 The settings in detail
12
6
12
16 17
24 h
18
24 h
CC1U7471en