Boiler/Burner Control - Siemens LMS14 User Manual

Albatros2 boiler management unit
Table of Contents

Advertisement

Burner running time min
Burner off time min
Building Technologies Division

6.11.7 Boiler/burner control

Line no.
Operating line
2241
Burner running time min
Here, set a period of time after burner startup during which the off time differential is
increased by 50%. This means that with similar heating up processes, the 2-position
controller switches off later. But this parameter setting does not guarantee continuous
burner operation for the parameterized period of time.
This option is used only when none of the 3 criteria for the dynamic switching
differentials is parameterized:
Dyn SD on setpoint (2464), Dyn SD with HC/DHW change (2466), and Dyn SD when
burner on (2467) are switched off.
Switching diff off max HCs (2456) and Switching diff off max DHW (2462) for the
maximum switch off differentials are thus deactivated.
The switch-off threshold is calculated based on the switching thresholds of the
respective Heating/DHW mode:
Switch-off threshold = setpoint + (min. switch-off differential) * 1.5.
Generally speaking, the use of dynamic switch-off thresholds seems more
advantageous. For this reason, the minimum burner running time should be seen in the
context of backward compatibility.
Line no.
Operating line
2243
Burner off time min
The minimum burner off time acts exclusively between successive startup cycles
resulting from space heating requests. It locks the boiler for an adjustable time. This
period of time is started after regular shutdowns or when the limit thermostat cuts out in
Heating mode. The 2-position controller initiates new startups resulting from space
heating requests only when this period of time has elapsed.
User Manual LMS14...
6 The settings in detail
205/617
CC1U7471en
07.05.2014