Siemens LMS14 User Manual page 432

Albatros2 boiler management unit
Table of Contents

Advertisement

Function value 2 H2
module 1, 2, 3
Key
Key
432/617
Building Technologies Division
Line no.
Operating line
6052
Funct value 2 H2 module 1
6060
Funct value 2 H2 module 2
6068
Funct value 2 H2 module 3
The linear characteristic is defined via 2 fixed points. The setting uses 2 pairs of
parameters for function value and voltage value (F
Example of heating demand DC 10 V
Flow temperature setpoint [°C]
F2 = 60
F2 = 80
F1 = 0
U1 = 0 V
0.15 V
Figure 93: H2 extension module – heating demand
F1
Function value 1
F2
Function value 2
U1
Frequency value 1
U2
Frequency value 2
If the input signal drops below the limit value of 0.15 V, the request for heat becomes
invalid, which means that it has no impact.
Example of pressure measurement at DC 10 V
Pressure value [bar]
4 bar
2 bar
1 bar
F1 = 0
0
U1 = 0.5 V
Figure 94: Input Hx H2 extension module – NO contact
F1
Function value 1
F2
Function value 2
U1
Frequency value 1
U2
Frequency value 2
User Manual LMS14...
6 The settings in detail
/U
nd F
1
1 a
2
U2 = 10 V
F2 = 40
F2 = 20
F2 = 10
Supply to Hx
U2 = 3.5 V
/U
).
2
Voltage at Hx
CC1U7471en
28.01.2015