Overtemperature Protection; Plant Hydraulics - Siemens LMS14 User Manual

Albatros2 boiler management unit
Table of Contents

Advertisement

Swimming pool temp max
Key
With solar integration
Building Technologies Division
6.9.3

Overtemperature protection

Line no.
Operating line
2070
Swimming pool temp max
If the swimming pool temperature reaches the limit set here, the collector pump is
deactivated. It is released again only when the swimming pool temperature drops 1 °C
below the maximum limit.
Figure 35: Overtemperature protection swimming pool temperature maximum
Line no.
Meaning
2070
TSbMax
Maximum storage tank temperature (buffer/DHW/swimming pool)
8900
TSb
Swimming pool temperature
6.9.4

Plant hydraulics

Line no.
Operating line
2080
With solar integration
No
Yes
The setting made here decides whether the swimming pool can be heated by solar
energy.
User Manual LMS14...
6 The settings in detail
195/617
CC1U7471en
07.05.2014