The load parameters converted to speeds are filed in the non-safety-related area and
must meet the following conditions:
Parameter
Required speed prepurging (9504)
Required speed ignition (9512)
Required speed LF (9524)
Required speed HF (9529)
Line no.
Meaning
4777.1
P_Vor
Output prepurging
4778.1
P_ZL
Ignition load output
4779.1
P_TL
Low-fire output
4780.1
P_VL
Output high-fire
9504
N_Vor_QAA
Speed required for prepurging
9512
N_ZL_QAA
Speed required for ignition
9524
N_TL_QAA
Speed required for low-fire
9529
N_VL_QAA
Speed required for high-fire
The values of fan speed (Fan speed heating max (2441), Fan speed full charging max
(2442), Fan sp start value inst WH (2443), Fan speed DHW max (2444) and Controller
delay speed (2452)) are limited to Required speed LF (9524) and Required speed HF
(9529).
The linear equation y = m*x +b with m = Fan output/speed slope (9626) and b = Fan
output/speed Y-section (9627) is used to calculate the required speed based on the
preset output.
User Manual LMS14...
6 The settings in detail
Safety-related parameter
PrepurgOutpLimOEM [4777.1]
IgnitionOutpLimOEM [4778.1]
PartialLoad OutLimOEM [4779.1]
HF outp OEM limit [4780.1]