Building Technologies Division
Safety limit thermostat
- Voltage
- Current
- Cable length
Fuel valve
- AC output
- Current
Note!
A fuel valve with rectifier may be connected to the fuel valve output only if
approved by Siemens!
In this case, additional protective measures inside the LMS14... must be taken
(optional components)
RAC output (optional
components)
- Output
General data on connection of
fuel valve
- Cable length
- Capacitive extra circuit or surge
voltage limiting protective
elements
External ignition module
- Voltage
- Current
- Cable length
-Starting current
In terms of switching performance, every external ignition module used must be
approved by Siemens!
Fan control
User Manual LMS14...
8 Technical data
AC 230 V
5 mA...1 A, cos >0.6
Carrying power to the fuel valve and
ignition
<1 m
AC 230 V +10%/-15%
Valve must still open at AC 175 V
5 mA...0.5 A, cos >0.6
RAC 230 V +10%/-15% 100 Hz
Valve must still open at RAC 175 V
Max. 20 W, cos >0.9
Max. 1 m for AC/RAC
Max. 3 m if cable is routed separately (to avoid
capacitive coupling)
Not permitted
AC 230 V +10%/-15%
5 mA...0.5 A, cos >0.6
Full ignition required at AC 175 V
Max. 1 m
Max. 3 m if cable is routed separately (to avoid
capacitive coupling)
Max 1 A
For fans driven by mains-powered DC motor
Refer to separate Siemens specification:
Spezifikation_LMU5x_TrafoGebläse_de_VX.Y.doc
(mandatory)
CC1U7471en
28.01.2015