Ext'n 24-hour heating limit
Building Technologies Division
The respective heating period is shortened or extended by changing the setting.
Increase:
Heating mode will start earlier.
Changeover to ECO later.
Decrease:
Heating mode will start later.
Changeover to ECO earlier.
Note!
The function is not active in operating mode Continuously Comfort temperature
The display shows ECO
To give consideration to the building's thermal dynamics, the outside temperature
is attenuated
Line no.
HC1
HC2
HC3
733
1033
1333
The 24-hour heating limit is extended by giving consideration to the composite outside
temperature when the heating is switched on. Alternatively, the heating can be
switched on again solely depending on the current outside temperature.
No
The 24-hour heating limit takes effect solely depending on the current outside
temperature.
Yes
The 24-hour heating limit takes effect as described under 24-hour heating limit,
depending on both the current and the composite outside temperature.
User Manual LMS14...
6 The settings in detail
Operating line
Ext'n 24-hour heating limit
No
Yes
141/617
CC1U7471en
07.05.2014