Albatros2 boiler management unit
Table of Contents

Advertisement

Operator unit
1620
Release
24h/day ¦ Time programs HCs ¦ Time program
4/DHW
1630
Charging priority
Absolute ¦ Shifting ¦ None ¦ MC shifting, PC
absolute
1640
Legionella function
Off ¦ Periodically ¦ Fixed weekday
1641
Legionella funct periodically
1642
Legionella funct weekday
Monday ¦ Tuesday ¦ Wednesday ¦ Thursday ¦
Friday ¦ Saturday ¦ Sunday
1644
Legionella funct time
1645
Legionella funct setpoint
1646
Legionella funct duration
1647
Legionella funct circ pump
Off ¦ On
1660
Circulating pump release
Time program 3/HC3 ¦ DHW release ¦ Time
program 4/DHW ¦ Time program 5
1661
Circulating pump cycling
Off ¦ On
1663
Circulation setpoint
1680
Optg mode changeover
None ¦ Off ¦ On
Consumer circuit 1
1859
Flow temp setp cons request
1874
DHW charging priority
No ¦ Yes
1875
Excess heat draw
Off ¦ On
Building Technologies Division
Operating line
ACS420
DHW Release
24h/day ¦ Heating programs with forward
shift ¦ Time switch program 4
DHW Charging Priority
Absolute ¦ Shifting ¦ None (parallel) ¦
Shifting, absolute
Legionella function
Off ¦ Periodically ¦ Fixed Weekday
LegioFunctPeriodicity
LegioFunction Day
Monday ¦ Tuesday ¦ Wednesday ¦
Thursday ¦ Friday ¦ Saturday ¦ Sunday
Time LegioFunkt
LegionellaFunctSetp
DwellTimeLegFunctSetp
CirculPumpOpLegioFunct
Off ¦ On
DHW CircPump Release
Time switch program 3 ¦ DHW release ¦
Time switch program 4 ¦ Time switch
program 5
DHW CircPump cycling
Off ¦ On
DHW Circ Setpoint
OptgModeCh'over DHW
None ¦ Off ¦ On
FlowTSetpConsReq 1
DHWChargPrioCC1
No ¦ Yes
Overtemp drop CC1
Off ¦ On
User Manual LMS14...
5 Handling
ACS700/ACS790
DHW release
24h/day ¦ Heating programs with forward
shift ¦ Time switch program 4
DHW charging priority
Absolute ¦ Shifting ¦ None (parallel) ¦
Shifting, absolute
Legionella function
Off ¦ Periodically ¦ Fixed weekday
Legionella function periodicity
Legionella function day
Monday ¦ Tuesday ¦ Wednesday ¦
Thursday ¦ Friday ¦ Saturday ¦ Sunday
Time for legionella function
Legionella function setpoint
Dwelling time at legionella function
setpoint
Circul. pump operation during
legionella func
Off ¦ On
DHW circulating pump release
Time switch program 3 ¦ DHW release ¦
Time switch program 4 ¦ Time switch
program 5
DHW circulating pump cycling
Off ¦ On
DHW circulation setpoint
Operating mode changeover DHW
None ¦ Off ¦ On
Flow temp setp cons request 1
DHW charging priority consumer
circuit 1
No ¦ Yes
Overtemperature drop consumer
circuit 1
Heating programs
with forward shift
Shifting, absolute
Fixed weekday
3
1
7
Monday
  
   / 00:00 23:50
65
55
95
   / 10
30
360
On
DHW release
On
45
8
80
Off
70
8
120
Yes
On
CC1U7471en
-
-
-
Days
hh:mm
°C
Min.
-
-
-
°C
°C
55/617