Siemens LMS14 User Manual page 533

Albatros2 boiler management unit
Table of Contents

Advertisement

Remote reset SLT
Remote reset air
Rem res extran light
Remote reset flame
AdvWindLossFlameHis
Additional parameters
Building Technologies Division
Line no.
Operating line
[4495.1]
Remote reset SLT
No
Yes
Locking error caused by the safety limit thermostat (SLT), irrespective of electronic or
mechanical safety limit thermostat.
Line no.
Operating line
[4496.1]
Remote reset air
No
Yes
Locking error caused by the air pressure switch (LP error).
Line no.
Operating line
[4497.1]
Rem res extran light
No
Yes
Locking error due to detection of extraneous light.
Line no.
Operating line
[4498.1]
Remote reset flame
No
Yes
Locking error due to erroneous flame detection or loss of flame during operation.
Line no.
Operating line
[6664.1]
AdvWindLossFlameHis
No
Yes
No
The Loss of flame error message is not written to the history if the cause is adverse
wind. The error handling approach/error response remains unchanged.
Yes
The Loss of flame error message is always written to the history.
At low speed it is highly probably that adverse wind is the cause of the loss of the flame.
For this reason, the AdvWindStartSp [4507.1] parameter is used as the suppression
criterion. If the current speed is lower than AdvWindStartSp [4507.1] when loss of flame
occurs, the error message is not written to the history.
Note!
Similarly, loss of flame at low speed (speed < AdvWindStartSp [4507.1]) not caused
by adverse wind is not written to the history.
Note!
Error messages resulting in a lockout will continue to be written to the history.
Consequently, the Loss of flame during operation elapsed repetition counter fault
entry may be written to the history but the associated losses of flame are not.
Line no.
Operating line
[4507.1]
AdvWindStartSp
User Manual LMS14...
6 The settings in detail
533/617
CC1U7471en
28.01.2015